Products - CDW6i Air Circuit Breaker
CDW6i Air Circuit Breaker

CDW6i series air Circuit Breaker (hereinafter referred to as breaker) is suitable for the circuit of AC 50Hz with rated voltage 400V, 690V and rated current up to 6300A.It is mainly used to distribute electric energy and protect circuits and power supply equipment from over-load, under-voltage, short-circuit and single-phase earthing. With intelligent and selective protection functions, the breaker can improve the reliability of power supply, and avoid unnecessary power failure. The breaker is applicable for power stations,factories,mines(for 690V) and modern high-buildings,especially for the distribution system of intelligentized building.This breaker conforms to IEC60947-2 and GB14048.2.The whole series have past CCC certification and CB certification of SEMKO.


Environment conditions for operation:

Environmental temperature condition:-5oC ~+40oC; 

The average value within 24h shall not exceed +35(Speial situation excluded )

Relative humidity at +40oC. Shall not exceed 50%. Higher humidity is permissible at lower temperature condition. When the highest monthly average relative humidity is 90% the lowest monthly average temperature of this month is +25oC.

And consider the influence of dew on product surface due to temperature changes

The breaker should be installed caccording to the requirements on the instruction manual.

The vertical inclination degree shall not exceed 5o


Structure: 

Drawer type breaker and fixed type breaker

image.png


Installation and Usage :

Unload the breaker from the soleplate of package-box. if it is drawer type, firstly pull out the handle from under the drawer-base of breaker, and plug it into the hole on central section of plastic cover under the drawer-base crossbeam, anticlockwise turns the handle, breaker body will slowly slide along the outside of drawer-base. When the guide-rod points to separated position and handle can't be rotated any longer, pull out the handle and firmly grasp the aluminum handle on drawer-base, pull out the breaker body and remove it from drawer-base.


Check the insulation resistance with a 500V merger, resistance should not be less than 20MQ when ambient temperature is 20oC¡À5oCand relative humidity is 50%-70%, otherwise have it dried. Put the breaker (fixed-type) or drawer-base (drawer-type) onto the installation- bracket, and make it fixed, directly connect the bus wire of main circuit to the bus wire of fixed-type circuit breaker, alternatively put breaker body onto the guild rail of drawer-base. Plug the place, and then connect the bus wire of main circuit to bus wire of drawer-base. Wire the secondary circuit according to electric principle diagram. Note: something like bolts, nuts. 


Gaskets shouldn't be left inside the drawer-base to avoid being blocked. Usage and operation Check the rated voltage of the following components whetherconforms to the power voltage or not .such as under voltage release,shunt releaseclosing electromagnet,motor-driven mechanism and intelligent controller Maintenance Check the technical index on time or and some lubricating oil.,etc. This breaker structure is arranged vertically and modularized composition with each function=cell separated, which make the maintenance easy.it has compact structure, reliable operation and strong free maintenance capability. Please check the technical parameters on the nameplate accordance with the reauirements of order before installation


Making the secondary circuit power, the motor-driven mechanism can store energy automatically until hearing the click and energy stored indicating on the panel. Otherwise press the storage handle for 6 times until hearing the click and the indicator display energy stored and the closing operation can be realized either by closing electromagnet or manual button.


Main teachnical parameter:

image.png

image.png