Products - BY20 Surge protective device
BY20 Surge protective device

Ethernet Lightning Protector

Product Details



BY20 Surge protective device


1
BY20-40/4


Usage and application scope

BY20 type surge protective device (short name "SPD") is suitable for AC 50/60 Hz,380V and the following electric power systems,such as TT, IT, TN-S, TN-C, TN-C-S. It protects the electric network shocked by the thunder or over voltage .

Working condition:

1.Height: not more than 2000m

2. Operating temperature : normal -5~+40˚C Enlarge range: -40~+80˚C

3. Relative humidity: on condition that room temperature 30%~90%

4. Installed at no notability shocked and virated place

5. Don't be contained in explosion medium,the medium such as air and dust (including conduction dust ) shouldn't come to the degree that can corrode metal or damage insulation. 


Model and meaning

2


Tripping device

There's tripping device designed on the modular of the protector. When the protector is over heat or shocked, the tripping device can automatically separate it from the electric net, at the same time showing the indication signal. It's green when the protector is normal, red when tripping.

Remote signaling contact 

The products can be produced available with the accessory of remote signaling contact. If one or more of modular of the protector is in malfuction, the contact will be closed, and sending the malfunction signal.

Principal parameters 

Maximum continuous operating voltage : Uc 275 440 V~

Test grade:II

Voltage protect level: Up≤ 1.2 1.8 2.0 kV

Maximum discharge current : (8/20μS) Imax 12 15 40 62kV 

Nominal discharge currrent: (8/20μS) In 8 5 15 30kA

Remote communication terminal parameter 


Type of remote communication terminal


Active

Terminal normal power

UN/IN

AC: 250V/0.5A DC: 250V/0.1A, 125V/0.2A, 75V/0.5A

Conductor section


Maximum single line: 1.5mm2


Main Structure and Operating Principle
n three-phase four- line system , three phase lines and one zero line are connected protective device to the earth cable . (figure 1 ) . In normal situation , the protective device is high resistance , when the over voltage brings for electric network shocked by thunder or other reasons , the protective device will rapidly transmit in ns , then lead the voltage into earth and protect the electric equipment . As the surge voltage through the protective device and after disappear it will recover to high resistance and not influence the normal operating.

3


Technical Parameters : 

Item

8-275

8-440

15-275

40-440

40-275

40-440

65-275

65-440

Maximum continuous operating voltage

Uc

275V~

440~

275V~

440V~

275V~

440V~

275V~

440V~

Nominal discharge currrent:

In

2

2

5

5

15

15

20

20

Maximum discharge current

Imax

8

8

15

15

40

40

65

65

Voltage protect level Up

5kA

≤1.2kV

≤1.8kV

≤1.2kV

≤1.8kV

≤1.2kV

≤1.8kV

≤1.5kV

≤2.0kV

Response time ns

≤25ns

Max. fuse intensity

125AgL/Gg

100AgL/Gg

Short circuit current intensity

16AgL/Gg

25AgL/Gg

50AgL/Gg80AgL/Gg

Operating temperature area

40˚C ~+ 80˚C

Conductor section

Min 1.5mm?sibgle lead, max. 35mm multi-twisting lead/35mm single laed

Installation frame

35mm rail

Out case

red hot shrink material

Protection class

IP20

Dimension

one stnadard module width 


Installation
1. It is installed by standard 35 mm rail.
2. The earth cable should choose the double color wire 4mm2 whose length is not longer than 500 mm.
3.To avoid the influence to the electric net after the protector is in malfuction, the protector connected to L line should be in series connect with a fuse. The appearance and installation dimension refer to the Fig. 3.

4


Adjustment, operation, maintenance
1. There's no need to adjust the protector after installation.
2. The protector can automatically protect the electric net should it's installed rightly.
3.When operating, check whether the modular scutcheon is red, at the same time check whether the indication red light is lighting, then can change the malfunction device.


Hot Tags: ethernet lightning protector, customized, wholesale, quality, discount, low price, in stock, latest design, easy-maintainable, latest design Panel VoltmeterQuality Electric Power Timerlatest design AC Outdoor Unit Contactorlatest design All Pole Isolating SwitchQuality Push Button Starterlatest design Double Power Socket


BY20 Surge protective device Prev :
BY20 Surge protective device Next :CTKB-IV current transformer protector